Generators · sizing
How to size a generator
The most common mistake when buying is to add up the rating plate powers of the loads and choose a generator with no margin. Such a setup works until the fridge or the pressure booster pump starts for the first time.
kW and kVA are not the same thing
Active power (kW) does the work, apparent power (kVA) loads the alternator windings. The two are linked by the power factor: kW = kVA × cos φ. Small single-phase generators are usually rated in kW at cos φ = 1, three-phase ones often in kVA at cos φ = 0.8. A 10 kVA generator at cos φ = 0.8 delivers 8 kW of active power.
Motor starting current
An induction motor started direct-on-line draws several times more current at start-up than when running. For sizing, a power multiplier is used:
| Load | Starting multiplier |
| Heating elements, incandescent lamps, kettle | 1 |
| Power tools with a universal (brushed) motor | 1.5–2 |
| Fridge, freezer, circulation pump | 2–3 |
| Pressure booster pump, compressor, concrete mixer | 3–5 |
A simple method
- Add up the power of all loads running at the same time.
- Add the starting surge of the largest motor (power × multiplier − power).
- Add a 20–30% margin to the running power. A generator that runs at 100% all the time wears faster and holds its voltage less well.
Check both power figures in the datasheet. The generator delivers its rated power continuously and its maximum power only briefly, for example while a motor starts. The AGP6000E-T has 6 kW maximum power and 5.5 kW rated power, so plan the continuous load for 5.5 kW.
Generators · voltage regulation
AVR, capacitor or inverter
The method of voltage regulation determines what can safely be connected to a generator.
| Regulation | Voltage stability | Best suited to |
| Capacitor | approx. ±5–10% | Tools, heaters, site lighting |
| AVR | approx. ±1–3% | Home, workshop, central heating boiler, home electronics and appliances |
| Inverter | approx. ±1%, low distortion | Sensitive electronics, camping, quiet running at light load |
How an AVR works
The automatic voltage regulator measures the output voltage and adjusts the excitation current of the alternator. When the load increases and the voltage starts to drop, the AVR raises the excitation. The response takes a fraction of a second, which is why a generator with AVR copes well with motors being switched on.
What an AVR cannot do
An AVR does not regulate frequency. The 50 Hz is set by the engine speed governor: a two-pole alternator gives 50 Hz at 3000 rpm. An overloaded engine slows down and the frequency falls regardless of the voltage regulator.
An inverter generator rectifies the alternator output and synthesises the sine wave electronically, so the engine speed can follow the load. This gives quieter running and lower fuel consumption at light load, but at higher power ratings the solution is considerably more expensive.
Engines
The generator engine: design and maintenance
Generators up to 10 kW are most often driven by an air-cooled four-stroke OHV petrol engine. A mechanical centrifugal governor holds about 3000 rpm by closing and opening the throttle according to the load.
Petrol, diesel, gas
- Petrol: lower purchase price, easy starting in winter, low weight. A good choice for emergency and occasional use.
- Diesel: lower fuel consumption and longer service life, but higher price, weight and noise. Pays off when running for many hours.
- LPG / natural gas: the fuel does not age in the tank and the exhaust is cleaner. Output is usually several to a dozen or so percent lower than on petrol.
Maintenance that gets forgotten
- Check the oil before every start. Carry out the first oil change after running-in and the following ones at the intervals given in the engine manual.
- The low oil level sensor cuts the ignition. If the generator will not start on sloping ground, this is often the reason.
- In dusty conditions (building sites, grinding), clean the air filter several times more often than the schedule states.
- Replace the spark plug preventively. It costs little and is the most common cause of difficult starting.
Petrol blended with ethanol deteriorates within a few months. Before a longer period out of use, close the fuel tap and let the engine run until the carburettor is empty.
Generators · phases
Single-phase or three-phase
A three-phase generator is not simply a “more powerful” version of a single-phase one. It is a different machine with different limitations.
When 230 V is enough
If all your loads have an ordinary plug, choose a single-phase generator. The whole output is then available in one circuit: a 6 kW generator will supply a 5 kW load without any workarounds.
When 400 V is needed
Three-phase motors (saws, compressors, concrete mixers, submersible pumps), welders and induction hobs wired for a three-phase supply require three phases.
The unbalanced load trap
In a three-phase generator the power is divided between three windings. As a rule, about one third of the rated power can be drawn from a single phase. A 10 kW generator will supply a 7 kW three-phase motor, but a 5 kW single-phase heater will overload one phase. Single-phase loads have to be distributed as evenly as possible across L1, L2 and L3.
Some generators state a separate rated current for 230 V and 400 V operation. In the AGP10000E-T datasheet this is 39.1 A at 230 V and 13.0 A per phase at 400 V. Before buying, find out how the particular model supplies single-phase loads.
For a house with a three-phase installation but no 400 V loads, a single-phase generator connected through a changeover switch that feeds all three phases from one is often the better solution. This requires the three-phase loads to be disconnected and the installation to be assessed by an electrician, because the neutral conductor then carries the sum of the currents.
Generators · installation
Connecting a generator to the house installation
A generator may supply a house only through an arrangement that makes simultaneous connection to the public grid physically impossible.
Mains–0–generator changeover switch
A manual three-position changeover switch (I–0–II) fitted in the distribution board is the simplest and most reliable solution. The 0 position guarantees a break between the two sources. The generator is connected to an appliance inlet, with the pins on the building side.
Automatic transfer switch (ATS)
An automatic transfer switch detects loss of mains voltage, starts a generator fitted with an electric starter, transfers the supply and returns to the initial state once the mains is back. It requires a generator with E-Start and a battery in good condition.
What you must not do
- Do not feed the installation through an ordinary socket with a “plug-to-plug” lead. The pins of the plug are then live, and when the mains returns the generator is destroyed.
- Without a changeover switch, voltage from the generator can pass through the transformer onto the line and electrocute a lineman repairing the fault.
The connection of a generator to a building installation must be carried out by a qualified electrician, who also selects the protection against electric shock and the earthing. It is advisable to notify the network operator that a standby source has been connected.
Stabilisers
Voltage stabilisers: types and sizing
A stabiliser keeps the output voltage close to 230 V when the mains voltage fluctuates, for example at the end of a long rural line or where there is a lot of solar PV generation in the area.
| Type | Principle | Accuracy | Notes |
| Relay | Autotransformer with taps switched by relays | approx. ±5–8% | Fast and inexpensive, stepped regulation, audible clicks |
| Servo | Brush moved along the winding by a motor | approx. ±1–3% | Stepless regulation, slower response, the brush wears |
| Thyristor (triac) | Taps switched by semiconductors | approx. ±3–5% | No moving parts, very fast, more expensive |
Sizing
Stabiliser power is stated in VA. For loads with a motor, allow a starting margin in the same way as for a generator. Note that at low input voltage the permissible power of many stabilisers falls, sometimes by half.
What a stabiliser will not do
- It will not keep the supply going during a power cut. That is the job of a UPS or a generator.
- It will not correct the frequency or the voltage waveform.
- Downstream of a generator with AVR it is usually unnecessary, and two regulators in series can set each other oscillating.
UPS
UPS: three topologies and their applications
An uninterruptible power supply keeps the loads running for the time needed to shut them down safely or to start a generator.
| Topology | How it works | Transfer time | Application |
| Off-line (VFD) | Load supplied from the mains, inverter starts on mains failure | a few to a dozen or so ms | Home computer, router |
| Line-interactive (VI) | As off-line, with a circuit that corrects the mains voltage | a few ms | Office, small servers, central heating boiler |
| On-line (VFI) | Double conversion: load supplied from the inverter at all times | 0 ms | Server rooms, automation, medical equipment |
Pure and “modified” sine wave
On battery, inexpensive units produce a stepped square wave. The switched-mode power supplies of computers tolerate it, but circulation pump motors and boiler controllers do not. For a central heating boiler, choose a UPS with a pure sine wave output.
Power and backup time
A UPS has two power ratings: apparent (VA) and active (W). What matters is the one the loads exceed first. Backup time depends on the battery capacity and increases non-linearly as the load decreases. Gel and AGM batteries are usually replaced every 3–5 years.
UPS · operation with a generator
UPS and generator in one system
The UPS covers the first minutes of an outage, the generator takes over the supply for hours. It is a natural combination which, in practice, often refuses to work without preparation.
Why the UPS “does not see” the generator
A UPS assesses the voltage and frequency at its input. If the generator, under a varying load, deviates from 50 Hz by more than the UPS allows, the UPS treats the source as unreliable and stays on battery until the battery is discharged.
How to set it up
- Oversize the generator. For an on-line UPS, the generator is rated at 1.5–2 times the UPS power, because the UPS rectifier draws a distorted current and charges the batteries as well.
- Choose a generator with AVR. Capacitor regulation copes poorly with a rectifier load.
- In the UPS settings, widen the frequency tolerance window or enable generator mode, if the manufacturer provides one.
- Limit the battery charging current while running on the generator.
- Switch the loads on in stages: the UPS first, then the remaining loads.
Before the storm season, test the whole system: switch off the mains supply, start the generator and check that the UPS returns from battery to the generator supply.
Generators · domestic installations
Gas boiler, heat pump and solar PV on a generator
Gas boiler
A boiler needs little power, usually 100–200 W, but it is demanding. Ionisation flame monitoring measures the current flowing to the earthed burner. A generator normally has an isolated neutral point, so the measuring circuit is not completed and the boiler reports a flame fault even though the voltage is correct. The solution, either a neutral-to-earth (N–PE) bond on the generator side or an isolating transformer, is selected by an electrician to suit the earthing system of the building.
Heat pump
An inverter-driven compressor starts gently, but the auxiliary heating element can draw several kilowatts. Before sizing the generator, check the maximum power draw of the whole unit and whether the heating element can be locked out during emergency operation.
Solar PV
A grid-tied (on-grid) inverter shuts down when the mains fails; this is its anti-islanding protection. Do not try to “keep it alive” with a generator: the inverter may treat the generator as the grid and feed power back into it, which ends in damage to the regulator or the alternator. Only hybrid inverters with a dedicated generator input work safely with a generator.
Operation
Safe operation and storage
Where to run it
- A generator must be run outdoors only. Carbon monoxide is odourless and also builds up in a garage with the door open.
- IP23 means protection against water sprayed at an angle of up to 60° from the vertical. The generator may stand under a roof or canopy, but not in a downpour and not in a puddle. The letter M indicates that the test was carried out with the machine running.
- Keep at least one metre of clear space around the unit. An air-cooled engine overheats in a tight enclosure.
Fuel and cables
- Refuel with the engine switched off and cooled down.
- Unwind an extension reel completely. A coiled cable under load heats up and melts its insulation.
- Select the conductor cross-section to suit the current and the length: 1.5 mm² is sufficient for short runs up to 16 A, for several tens of metres choose 2.5 mm².
Ready for an outage
- Once a month, run the generator under load for ten to fifteen minutes. Running at no load is not enough.
- On models with electric start, keep the battery charged. A flat battery is the most common reason a generator will not start on the day of an outage.
- Keep a supply of fresh fuel in a jerrycan and replace it every few months.